Density Measurement Option
*
Installation Guide
T5 Series
Important: Thedensityoatisveryfragile.Donottodamagetheoat’scoating;itprovideselectricalcharacter-
isticstoavoidstaticdischargeandpreventproductabsorption(whichwillcauseincorrectreadings).
Overview
T5 series consoles with magnetostrictive probes (TSP-LL2) serial # 6XXXXX can have the Density Measurement Option
enabled. This feature measures and reports the density of product in a tank using the same probe by adding an additional
oat (called ‘density oat’) that will be located around and below the product oat (close to the surface of the product). The
Density Measurement Option can be useful to help a site determine the quality of the product deliveries that they receive
and whether or not they’ve been altered in any way.
Density is calculated based on the distance between the product oat and the density oat. Due to high accuracy require-
ments, the product oat and the density oat will be calibrated as a pair when they are shipped from the factory and must
not be separated in the eld. If either oat is damaged, both will have to be replaced at the same time. Each pair of oats will
be provided with a calibration constant that needs to be programmed into the ATG in addition to the probe gradient.
The oat set will also include a water oat, which does not affect density measurement and may or may not be installed.
All oat sets will include one of each of the following: 3" product oat
4" density oat
4" water oat
The density oat part numbers are:
PartNumber Description
TSP-IGF4D 4" gasoline density oat set
TSP-IDF4D 4" diesel density oat set
TechnicalSpecications
ProbePartNumber DensityMeasurementRange
TSP-IGF4D 690-800 kg/m
3
TSP-IDF4D 790-900 kg/m
3
DensityMeasurementAccuracy +/- 1.0 kg/m
3
DensityMeasurementResolution +/- 0.1 kg/m
3
MinimumDetectableProductLevel without water oat – 170 mm (6.7")
with water oat – 270 mm (10.7")
*U.S.Patent7,278,311
Internationalpatentpending
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Density Measurement Option

1Density Measurement Option*Installation GuideT5 SeriesImportant: Thedensityoatisveryfragile.Donottodamagetheoat’scoating;itprovides

Seite 2 - Installation

2InstallationThe selection and the installation of the probe is exactly the same as in cases of regular level measurement. The only dif-ference is in

Seite 3 - Figure5

3SetupSetup can be performed using either a local user interface (LCD on the console) or a web interface (remotely connecting with Tank Sentinel Anywa

Seite 4 - WebInterface

4WebInterfaceDisplayDensity is calculated each time product volume is calculated. Density is displayed in kg/m3 or g/cm3.

Seite 5 - PrintoutfromATGconsole

5ReportsThe Inventory Report will display a column with density metrics.PrintoutfromATGconsolewithDensitystatusPrintoutfromHPUSBprinterwi

Seite 6 - FieldCalibrationProcedure

6FieldCalibrationProcedureOver time a oat’s weight can change due to sediment deposits, which can lead to systematically inaccurate readings. These

Seite 8 - ©2007 FFS 000-0527 Rev. B

©2007 FFS 000-0527 Rev. B